RSS گلند کابل ضدانفجار آرمور دار
Application
Outdoor or indoor use.
For use with single wire armour ‘W’, wire braid ‘X’ and steel tape armour ‘Z’ elastomer and plastic insulated cables with a lead inner sheath.
For particular use with:-
a) Cables that are not effectively filled, compact and/or circular, have tape bedding or have hygroscopic fillers.
b) Cables that exhibit ‘cold flow’ characteristics.
c) Enclosures containing an ignition source in gas group IIC areas or containing an ignition source in a Zone 1 area.
Features
Provides a barrier seal between the individual insulated cores within the cable and prevents entry of the products of an explosion into the cable.
Assembly of the cable gland compresses and distributes the compound evenly to create a barrier seal at the point of entry into the enclosure.
The compound chamber may be separated from the cured compound to ensure that the chamber has been effectively filled. If required, external voids can be repaired.
Provides armour clamping, using one clamping arrangement for all armour/braid types.
Provides a seal and an electrical bond on the cables lead inner sheath.
Provides an outer deluge seal to prevent moisture ingress to the cable armour/braid.
Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer sheath.
Materials & Finishes
The ICG 653/Universal/L cable gland is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminum. Brass NPT entries are nickel plated as standard.
Category: Cable Glands
Product code: RICG 653/Universal/L
5 stars, based on 1 reviews
CABLE GLAND SELECTION TABLE | |||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Size Ref. |
Entry Thread Size |
Cable Acceptance Details |
‘G’ Compressed Length |
Hexagon Dimensions |
|||||||||||
Inner Sheath/Cores |
‘B’ Outer Sheath |
‘C’ Armour/Braid |
|||||||||||||
Metric |
NPT * |
‘D’ Max. Over Cores |
‘E’ Inner Sheath |
NOTE 1 Max. No. Of Cores |
NOTE 2 Max. No. Of Cores |
Across Flats |
Across Corners |
||||||||
Standard | Option | Min. | Max. | Min. | Max. |
Orientation 1 |
Orientation 2 |
||||||||
Os | M20 | ½" | - | 8.5 | 4.0 | 10.0 | 12 | 6 | 5.5 | 12.0 | 0.8 / 1.25 | 0 / 0.8 | 67.0 | 24.0 | 26.5 |
O | M20 | ½" | - | 8.5 | 4.0 | 10.0 | 12 | 6 | 9.5 | 16.0 | 0.8 / 1.25 | 0 / 0.8 | 67.0 | 24.0 | 26.5 |
A | M20 | ¾" | ½" | 10.8 | 7.4 | 12.5 | 15 | 10 | 12.5 | 20.5 | 0.8 / 1.25 | 0 / 0.8 | 67.0 | 30.0 | 32.5 |
B | M25 | 1" | ¾" | 16.2 | 11.0 | 18.4 | 30 | 21 | 16.9 | 26.0 | 1.25 / 1.6 | 0 / 0.7 | 73.6 | 36.0 | 39.5 |
C | M32 | 1¼" | 1" | 21.9 | 14.0 | 24.7 | 42 | 42 | 22.0 | 33.0 | 1.6 / 2.0 | 0 / 0.7 | 78.0 | 46.0 | 50.5 |
C2 | M40 | 1½" | 1¼" | 26.3 | 21.0 | 29.7 | 60 | 60 | 28.0 | 41.0 | 1.6 / 2.0 | 0 / 0.7 | 82.4 | 55.0 | 60.6 |
D | M50 | 2" | 1½" | 37.1 | 27.0 | 41.7 | 80 | 80 | 36.0 | 52.6 | 1.8 / 2.5 | 0 / 1.0 | 88.7 | 65.0 | 70.8 |
E | M63 | 2½" | 2" | 47.8 | 39.0 | 53.3 | 100 | 100 | 46.0 | 65.3 | 1.8 / 2.5 | 0 / 1.0 | 92.7 | 80.0 | 88.0 |
F | M75 | 3" | 2½" | 59.0 | 51.0 | 64.0 | 120 | 120 | 57.0 | 78.0 | 1.8 / 2.5 | 0 / 1.0 | 99.4 | 95.0 | 104.0 |
All dimensions in millimetres (except * where dimensions are in inches). Metric entry threads are 1.5mm pitch as standard. Note 1: ATEX/IECEx certification only. Note 2: All other certification. |