RSS ترمینال باکس استنلس استیل
316 L Stainless Steel.
Category: Stainless Steel Enclosure
Product code: SS6
5 stars, based on 1 reviews
ENCLOSURE DISSIPATED WATTAGE | |||||
---|---|---|---|---|---|
Enclosure Type | Temperature Class | ||||
T6 40°C & T5 55°C | T6 55°C | T5 40°C | T6 65°C | T5 65°C | |
Size 6 Stainless Steel | 40 | 25 | 55 | 15 | 30 |
MAXIMUM QUANTITY OF ENTRIES PER FACE | |||||||||
---|---|---|---|---|---|---|---|---|---|
Thread Size | M16 | M20/O | M20/A | M25 | M32 | M40 | M50 | M63 | M75 |
Bottom Face C Quantity |
44 # | 42 | 32 | 26 | 14 | 11 | 6 | 4 | 3 |
Side Faces B & D Quantity |
56 # * | 54 | 40 | 33 | 18 | 14 | 8 | 5 | 4 |
# Serrated washers/locknuts with large outside diameters may foul on adjacent cable glands. * Serrated washers/locknuts must not foul on aperture wall. |
TERMINAL CAPACITY DATA | ||||||||
---|---|---|---|---|---|---|---|---|
Terminal Type | Conductor Size (mm²) |
Max. Volts |
Max. Physical Terminal Content |
Reduced Terminal Content At Max. Terminal Amps |
||||
Min. | Max. |
Terminal Quantity |
Amps |
Terminal Quantity |
Amps | |||
WDU 2.5 | 0.5 | 2.5 | 550 | 380 | 4 | 22 | 17 | |
WDU 4 | 0.5 | 4 | 690 | 320 | 5 | 20 | 22 | |
WDU 6 | 0.5 | 6 | 550 | 240 | 7 | 17 | 29 | |
WDU 10 | 1.5 | 10 | 550 | 200 | 11 | 15 | 40 | |
WDU 16 | 1.5 | 16 | 690 | 160 | 15 | 13 | 53 | |
WDU 35 | 2.5 | 35 | 690 | 120 | 25 | 10 | 87 | |
WDU 50 | 6 | 50 | 690 | 96 | 33 | 13 | 88 | |
WDU 70N | 10 | 70 | 690 | 50 | 54 | 9 | 134 | |
WDU 70/95 | 16 | 70 | 690 | 19 | 86 | 8 | 134 | |
WDU 70/95 | 16 | 95 | 690 | 19 | 97 | 11 | 134 | |
WDU 120/150 | 35 | 120 | 690 | 16 | 114 | 9 | 162 | |
WDU 120/150 | 35 | 150 | 690 | 16 | 120 | 10 | 162 | |
WFF 35 | 2.5 | 35 | 1100 | 38 | 48 | 16 | 76 | |
WFF 70 | 2.5 | 70 | 1100 | 16 | 100 | 13 | 116 | |
WFF 120 | 6 | 120 | 1100 | 12 | 152 | 11 | 162 | |
WFF 185 | 10 | 185 | 1100 | 9 | 212 | 7 | 234 | |
WFF 300 | 25 | 300 | 1100 | 9 | 255 | 6 | 316 | |
The enclosure is supplied with an integral internal/external earth stud assembly. The terminals listed are restricted to a minimum operating temperature of -50°C. |